An overview of the
GCS low-voltage withdrawable switchgear is suitable for the power plant, petroleum, chemical industry, metallurgy, textile, high-rise building distribution system. In large power plants, petrochemical system, such as high degree of automation, and computer interface, a three-phase ac frequency 50 Hz (60), rated voltage is 380 v, 660 v), rated current 4000 a, power supply system of power distribution and motor under centralized control, reactive power compensation using low-voltage power distribution equipment. Products comply with it - 1 "low-voltage complete switch equipment and control equipment", GB7251 "low-voltage complete switch equipment", ZBK36001 standards such as the "low voltage draw-out switchgear.
The main technical parameters
The rated working voltage: ac 380 v (660 v)
The rated insulation voltage: ac 660 v (1000 v)
Rated frequency 50 hz (60 hz)
Auxiliary circuit voltage rating: ac 220 v, 380 v; Dc 110 v, 220 v
The rated working current: horizontal bus: 4000 or less a vertical busbar: 1000 a
Maximum rated current short-term tolerance: horizontal bus: 80 ka 1 s vertical bus: 50 ka 1 s
Maximum rated current peak tolerance: horizontal bus: 170 ka vertical bus: 105 ka
The rated power frequency withstand voltage: 2500 v 1 min
Bus: three phase four wire system; Three-phase five wire
Protection grade: IP30, IP40
Installation dimensions (mm) wide * * deep high: 600 (800, 1000) * 800 * 2200 (1000)